Fill out our form with your model of interest and we'll send you a downloadable brochure or technical specifications document.
Our 4016 range gives you the versatility and heavy duty performance you need in today's power generation market. The Perkins 4016 engines feature 16 cylinders and a massive 61 litre displacement in both ElectropaK and Electro Unit variants. The 4016 range offers 1400-2500 kVA generator output. Our 4016 range engines have exceptional power-to-weight ratio and compact design, making them easy to transport and install.
The Perkins 4016 range gives you 1400-2500 kVA generator output. A key benefit of the 4016-61TRG engines is the option to have a…
Options for your 4016 range diesel engines include: • Tropical radiator, including water pipes, clips and hoses, fan, fan guard…
| Specification | Value |
| Gross Mechanical Output | 1269-2183 kWm |
| Typical Electrical Output | 1400-2500 kVA (1120-2000 kWe) |
| Rated Speed | 1500 rpm |
| Specification | Value |
| Prime | 1850-2250 kVA |
| Standby | 2000-2500 kVA |
| Baseload | 1400-1800 kVA |
| Specification | Value |
| Emissions | Fuel Optimised |
| Specification | Value |
| Number of Cylinders | 16 Vee |
| Bore | 160 mm |
| Stroke | 190 mm |
| Displacement | 61.1 l |
| Compression Ratio | 13.0:1 |
| Aspiration | Quad turbocharged and air-to-water charge cooled |
| Combustion System | Direct injection |
| Rotation from Flywheel End | Anti-clockwise |
| Cooling System | Liquid |
| Aftertreatment | - |
| Typical Alternator Efficiency | 95-96% |
| Switchable | No |
| Specification | Value |
| Length | 4.542 mm |
| Width | 2.185 mm |
| Height | 3.175 mm |
| Dry Weight | 7.783 kg |
| Specification | Value |
| Note 1 | *Final dimensions dependent on selected options |
| Specification | Value |
| Prime Power | Variable load. Unlimited hours usage with an average load factor of 80% of the published prime power over each 24 hour period. A 10% overload is available for 1 hour in every 12 hour operation. |
| Standby Power | Limited to 500 hours annual usage with an average load factor of 80% of the published standby power rating over each 24 hour period. Up to 300 hours of annual usage may be run continuously. No overload is permitted on standby power. |
| Baseload | Unlimited hours usage with an average load factor of 100% of the published baseload power. No overload is permitted on baseload power. |
Learn more information about the Perkins 4016-61TRG Electric Power Diesel Engine.
Download (2.22 MB, PDF)From pre-purchase consults to end-of-lifecycle benefits, Mantrac informs, advises and partners with you.
Speak with the Sales Team to learn the latest prices and information on products that can deliver value and help transform your business.
Find the perfect machine or equipment solution by contacting one of our local specialists. They are on standby, ready to help you solve your operational challenges.
Ask an Expert today!