Diesel Generator Sets
Cat C13 Generator Set
Minimum Rating 320 ekW
Maximum Rating 400 ekW
Emissions/Fuel Strategy EPA Stat Emergency Use
320 to 400 ekW Generator Set for Standby and Prime applications.
Cat Diesel Engine
Reliable, rugged, durable designField-proven in thousands of applications worldwideFour-stroke-cycle diesel engine combines consis…
Generator
Matched to the performance and output characteristics of Cat engines Industry leading mechanical and electrical design Industry le…
EMCP Control Panel
The EMCP controller features the reliability and durability you have come to expect from your Cat equipment. EMCP4 is a scalable c…
Design Criteria
The generator set accepts 100% rated load in one step per NFPA 110 and meets ISO 8528-5 transient response.
Single-Source Supplier
Fully prototype tested with certified torsional vibration analysis available
World Wide Product Support
Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer br…
Standard Equipment
Starting / Charging
- Charging alternator
- 24-Volt electric starting motor
Control System Controller
- EMCP 4.2
Certification
- EPA stationary emergency use
Base / Fuel Tank
- Audio and visual fuel alarm
Protection
- Coolant Level Sensor
- Safety Shutoff - Low Oil Pressure
- Safety Shutoff - High water temperature
- Safety Shutoff - Overspeed
Optional Equipment
Engine Air Cleaner
- Single Element
- Duel Element
- Heavy Duty
Muffler
- Industrial grade (10 dBA)
- Residential and Critical grade (25 dBA)
Starting and Charging
- Standard battery set
- Oversize battery set
Control System Controller
- EMCP 4.4
- Local annunciator
- Remote annunciator
- Discrete I/O module
- Device Server
- Volt free contact
- Earth (ground) fault relay
Generator
- Excitation - Self
- Excitation - Internal / AREP
- Excitation - PMG
- Oversize
- Coastal protection (CIP)
- Space heater control
- Output Voltages
Power Termination
- Power terminal strips
- Circuit Breakers
Enclosure
- Weather protective
- Sound attenuated
Certification
- UL2200 listed
- CSA 22.2
- Certification of Compliance - IBC Seismic
- Certification of Compliance - IBC Seismic and OSHPD
Extended Service Coverage
- 2 Year
- 3 Year
- 4 Year
- 5 Year
- 10 Year
Base / Fuel Tank
- Narrow skid
- Wide / Standard
- Sub tank base - UL and ULC listed
- Integral tank base - UL AND ULC listed
- Spill containment
- Overfill prevention valve
-
Generator Set Specifications
Minimum Rating 320 ekW Maximum Rating 400 ekW Voltage 208 to 600 Volts Frequency 60 Hz Speed 1800 rpm Emissions/Fuel Strategy EPA Stat Emergency Use -
Engine Specifications
Engine Model C13 ACERT In-line 6, 4-cycle diesel Compression Ratio 16.3:1 Aspiration Turbocharged Air to Air Aftercooled Governor Type Adem™A4 Fuel System MEUI Stroke 6.2 in Displacement 763 in³ Bore 5.12 in
Frequently Compared Machines
See how this model compares against similar machines to find the perfect match.
Service Solutions
We have an extensive team of experts to help you enhance every aspect of your operations.

Warranty & Guarantee

Technology

Financing
Get in Touch with
our Sales Team
Speak with the Mantrac Sales Team to learn the latest prices and information on products that can deliver value and help transform your business.
Speak with our local experts
Find the perfect machine or equipment solution by contacting one of our local specialists. They are on standby, ready to help you solve your operational challenges.

Mantrac Djibouti
DAMAL COMPLEX Route de la Siesta BP334) Djibouti Republique de Djibouti
Hotline: +253 21 34 34 08